SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the COB-ID for the emergency message (error telegram).
It corresponds to the CANopen objects:
- 1014 hex: COB-ID
Note: If, when downloading, the pre-set value 0 is downloaded, then the CANopen pre-set value 80 hex + Node-ID is
automatically set.
Online, the value 0 is rejected as, according to the CANopen Standard, COB-ID 0 is not permitted here.
The changeover of the node ID using the hardware switch at the Control Unit or per software has no effect on the
COB-ID EMCY. The saved value remains effective.
Description: Sets the node guarding parameter for the following CANopen objects:
- 100C hex: Guard Time
- 100D hex: Life Time Factor
The life time is derived by multiplying guard time by the life time factor.
Index: [0] = Time interval [ms] for new node guarding telegram
[1] = Factor for failure of the node guarding telegram
Dependency: Only adjustable if heartbeat time = 0 (heartbeat is disabled).
Refer to: p8606
Note: For p8604[0] = 0 and/or p8604[1] = 0, the node guarding protocol is not used.
Either node guarding or heartbeat can be used.
Description: Sets the time [ms] to cyclically send heartbeat telegrams.
The smallest cycle time is 100 ms.
When a 0 is written, then heartbeat telegrams are not sent.
Dependency: Only adjustable if guard time = 0 (node guarding disabled).
Refer to: p8604
Note: Corresponds to the CANopen object 1017 hex.
Either node guarding or heartbeat can be used.
p8603 CAN COB-ID Emergency Message / COB-ID EMCY Msg
CU_S110-CAN Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
p8604[0...1] CAN node guarding / Node guarding
CU_S110-CAN Can be changed: T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
p8606 CAN Producer Heartbeat Time / Prod Heartb Time
CU_S110-CAN Can be changed: T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 65535 [ms] 0 [ms]