Siemens SINAMICS S110 - p9568 SI Motion SAM velocity limit (processor 1); SI Mtn SAM v_limP1; p9570 SI Motion acceptance test mode (processor 1); SI Mtn Acc_mode; r9571 SI Motion acceptance test status (processor 1); SI Mtn acc_status

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter
List of parameters
1-580
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the velocity tolerance limit for the "SAM" function.
SAM is de-activated once the set velocity limit has been undershot.
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
For p9568 = p9368 = 0, the following applies:
The value in p9546/p9346 (SSM) is applied as the velocity limit for SAM.
Description: Setting to select and de-select the acceptance test mode.
Value: 0: [00 hex] De-select the acceptance test mode
172: [AC hex] Select the acceptance test mode
Dependency: Refer to: p9558, r9571, p9601
Refer to: C01799
Note: Acceptance test mode can only be selected if the motion monitoring functions, which are integrated in the drives,
are enabled (p9601.2/p9801.2).
Description: Displays the status of the acceptance test mode.
Value: 0: [00 hex] Acc_mode inactive
12: [0C hex] Acc_mode not possible due to POWER ON fault
13: [0D hex] Acc_mode not possible due to incorrect ID in p9570
15: [0F hex] Acc_mode not possible due to expired Acc_timer
172: [AC hex] Acc_mode active
Dependency: Refer to: p9558, p9570
Refer to: C01799
p9568 SI Motion SAM velocity limit (processor 1) / SI Mtn SAM v_limP1
SERVO_S110-CAN
(Safety rot),
SERVO_S110-DP
(Safety rot),
SERVO_S110-PN
(Safety rot)
Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 1000.00 [rpm] 0.00 [rpm]
p9570 SI Motion acceptance test mode (processor 1) / SI Mtn Acc_mode
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex 00AC hex 0000 hex
r9571 SI Motion acceptance test status (processor 1) / SI Mtn acc_status
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex 00AC hex -