Description: Displays the status word for the ramp-function generator (RFG).
Note: Re bit 02:
The bit is an OR logic operation - bit 00 and bit 01.
Description: Selects the faults for which automatic restart should not be effective.
Dependency: The setting is only effective for p1210 = 6, 16.
Refer to: p1210
Description: Sets the signal source to modify the automatic restart (AR).
Interconnections between the automatic restart and infeed:
With the following interconnection in the mode p1210 = 6, the automatic restart can respond to infeed faults:
BI: p1208[0] = r2139.3
With the following interconnection, in the mode p1210 = 4, the automatic restart can respond to line supply failure of
the infeed:
BI: p1208[1] = r0863.2
Index: [0] = Infeed fault
[1] = Infeed line supply failure
Dependency: Refer to: r0863, r2139
r1199.0...6 CO/BO: Ramp-function generator status word / RFG ZSW
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 1550, 3080,
8010
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Ramp-up active Yes No -
01 Ramp-down active Yes No -
02 RFG active Yes No -
03 Ramp-function generator set Yes No -
04 Ramp-function generator held Yes No -
05 Ramp-function generator tracking active Yes No -
06 Maximum limit active Yes No -
p1206[0...9] Set the fault number without automatic restart / Fault_No w/o AR
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
p1208[0...1] BI: AR modification infeed / AR modification
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0