List of parameters
Parameter
1-605
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Displays the number of the cross-checked data which has caused STOP F on the Control Unit.
Dependency: Refer to: r9895
Refer to: F01611
Note: A complete list of numbers for crosswise-compared data items appears in fault F01611.
Description: Displays the checksum over the checked Safety Integrated parameters on the Control Unit (actual checksum).
Dependency: Refer to: p9799, r9898
Description: Sets the checksum for the checked Safety Integrated parameters on the Control Unit (reference checksum).
Dependency: Refer to: r9798, p9899
Description: Sets the enable signals for safety functions on processor 2 that are integrated in the drive.
Not all possible settings may be permissible, depending on the Control Unit and Motor Module or Power Module
being used.
Dependency: Refer to: p9601, r9871
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: STO: Safe Torque Off
SMM: Safe Motion Monitoring
A change only becomes effective after a POWER ON.
r9795 SI diagnostics STOP F (Control Unit) / SI diag STOP F CU
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dynamic index: - Func. diagram: 2802
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r9798 SI actual checksum SI parameters (Control Unit) / SI act_checksum CU
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: 2800
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p9799 SI reference checksum SI parameters (Control Unit) / SI set_checksum CU
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: 2800
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
p9801 SI enable, functions integrated in the drive (processor 2) / SI enable fct P2
SERVO_S110-CAN Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 STO (SH) via terminals (Motor Module)
enable
Enable Inhibit 2810
02 Motion monitoring functions integr. in the
drive (Motor Module)
Enable Inhibit -