Siemens SINAMICS S110 - p2257 Technology controller, ramp-up time; Tec_ctrl t_ramp­up; p2258 Technology controller ramp-down time; Tec_ctrl t_ramp­dn; r2260 CO: Technology controller setpoint after ramp-function generator; Tec_ctr set aftRFG; p2261 Technology controller setpoint filter time constant; Tec_ctrl set T

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameter
1-347
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the ramp-up time of the technology controller.
Dependency: Refer to: p2252, p2258
Note: The ramp-up time is referred to 100 %.
Description: Sets the ramp-down time of the technology controller.
Dependency: Refer to: p2252, p2257
Note: The ramp-down time is referred to 100 %.
Description: Sets the setpoint after the ramp-function generator of the technology controller.
Description: Sets the time constant for the setpoint filter (PT1) of the technology controller.
p2257 Technology controller, ramp-up time / Tec_ctrl t_ramp-up
SERVO_S110-CAN
(Tech_ctrl),
SERVO_S110-DP
(Tech_ctrl),
SERVO_S110-PN
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]
p2258 Technology controller ramp-down time / Tec_ctrl t_ramp-dn
SERVO_S110-CAN
(Tech_ctrl),
SERVO_S110-DP
(Tech_ctrl),
SERVO_S110-PN
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [s] 650.00 [s] 1.00 [s]
r2260 CO: Technology controller setpoint after ramp-function generator /
Tec_ctr set aftRFG
SERVO_S110-CAN
(Tech_ctrl),
SERVO_S110-DP
(Tech_ctrl),
SERVO_S110-PN
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p2261 Technology controller setpoint filter time constant / Tec_ctrl set T
SERVO_S110-CAN
(Tech_ctrl),
SERVO_S110-DP
(Tech_ctrl),
SERVO_S110-PN
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]