List of parameters
Parameter
1-291
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Displays the interface mode of the PROFIdrive control words and status words.
Value: 0: SINAMICS
Dependency: Refer to: p0922, p2079
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: For p0922 (p2079) = 7, 9, 110, 111, p2038 is automatically set to 0 and cannot be changed.
Description: Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, an appropriate message is output.
Dependency: Refer to: F01910
Note: 0: The monitoring is de-activated.
Description: Sets the PROFIBUS Ident Number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with Ident Number 3AA0 hex).
Value: 0: SINAMICS
1: VIK-NAMUR
Note: Every change only becomes effective after a POWER ON.
Description: Displays the PROFIdrive PZD state.
Dependency: Refer to: p2044
p2038 IF1 PROFIdrive STW/ZSW interface mode / PD STW/ZSW IF mode
SERVO_S110-DP
(EPOS, Pos ctrl),
SERVO_S110-PN
(EPOS, Pos ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 0 0
p2040 Fieldbus interface monitoring time / Fieldbus t_monit
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1999999 [ms] 100 [ms]
p2042 PROFIBUS Ident Number / PB Ident No.
CU_S110-DP Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
r2043.0...2 BO: IF1 PROFIdrive PZD state / IF1 PD PZD state
CU_S110-DP,
CU_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dynamic index: - Func. diagram: 2410
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Setpoint failure Yes No -
01 Clock cycle synchronous operation active Yes No -
02 Fieldbus oper Yes No -