Parameter
List of parameters
1-258
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the signal source to activate/de-activate the "travel to fixed stop" function
1: Travel to fixed stop is active
0: Travel to fixed stop is inactive
Dependency: Refer to: p1542, r1543, p1544
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the speed threshold for the motoring/regenerative limit.
For speeds where the absolute value is less than p1546, then the following applies:
- For p1400.13 = 0: Motoring limit (speed threshold is compared to the speed actual value).
- For p1400.13 = 1: Regenerative limiting (speed threshold is compared to the speed setpoint).
Description: Displays the instantaneous stall power.
Dependency: Refer to: p0326
Note: The stall power is influenced by p0326, p0353, p0354 and p0356.
Description: For a positive edge, the actual torque (r0079[0]) at this instant in time is used instead of the torque offset from
p1532 as long as p1550 remains at 1.
p1545[0...n] BI: Activates travel to a fixed stop / TfS activation
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2520, 3617,
8012
P-Group: Commands Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p1546 Speed threshold motoring/regenerating / n_thresh mot/regen
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 20.00 [rpm]
r1549 CO: Stall power actual value / P_stall
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 5640
P-Group: Displays, signals Units group: 14_5 Unit selection: p0505
Not for motor type: - Scaling: r2004 Expert list: 1
Min Max Factory setting
- [kW] - [kW] - [kW]
p1550[0...n] BI: Transfer actual torque as torque offset / Accept act torque
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 9718.23