Siemens SINAMICS S110 - F07430 Drive: Changeover to open-loop torque controlled operation not possible; F07431 Drive: Changeover to encoderless operation not possible; F07432 Drive: Motor without overvoltage protection; F07433 Drive: Closed-loop control with encoder is not possible as the encoder has not been unparked

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of faults and alarms
Faults and alarms
3-1071
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
F07430 Drive: Changeover to open-loop torque controlled operation not possible
Message value: -
Drive object: SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction: OFF2 (NONE, OFF1, OFF3)
Acknowledge: IMMEDIATELY
Cause: For encoderless operation, the converter cannot change over to closed-loop torque-controlled operation (BI: p1501).
Remedy: Do not attempt to cover over to closed-loop torque-controlled operation.
F07431 Drive: Changeover to encoderless operation not possible
Message value: -
Drive object: SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction: OFF2 (OFF1)
Acknowledge: IMMEDIATELY
Cause: For closed-loop torque control, the converter cannot change over to encoderless operation (p1404).
Remedy: Do not attempt to change over to encoderless operation.
F07432 Drive: Motor without overvoltage protection
Message value: %1
Drive object: SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction: OFF2 (OFF1)
Acknowledge: IMMEDIATELY
Cause: In the case of a fault at maximum speed, the motor can generate an overvoltage that can destroy the drive system.
Fault value (r0949, interpret hexadecimal):
Associated Drive Data Set (DDS).
Remedy: Overvoltage protection can be implemented in the following ways:
- limit the maximum speed (p1082) without any additional protection.
The maximum speed without protection is calculated as follows:
Rotary synchronous motors: p1082 [rpm] <= 11.695 * p0297/p0316 [Nm/A]
Linear motors: p1082 [m/min] <= 73.484 * p0297/p0316 [N/A]
Rotary synchronous motors connected to a high-frequency converter: p1082 [rpm] <= 4.33165 * (-p0316 + square
root(p0316^2 + 4.86E-9 * (p0297 * r0313)^2 * (r0377 - r0233) [mH] * r0234 [µF]) / (p0297 * r0313^2 * (r0377 - r0233)
[mH] * r0234 [µF])
Linear motor connected to a high-frequency converter: p1082 [m/min] <= 0.6894 * (-p0316 + square root( p0316^2
+ 1.91865E-7 * (p0297 * r0313 * 3.1415)^2 * (r0377 - r0233) [mH] * r0234 [µF]) / (p0297 * r0313^2 * (r0377 - r0233)
[mH] * r0234 [µF])
Rotary induction motor connected to a high-frequency converter: p1082 [rpm] <= Maximum (2.11383E5 / (r313 *
square root((r0377 [mH] + r0382 [mH]) * r0234 [µF])) ; 0.6364*p0297*p0311[rpm] / p0304)
- use a voltage protection module (VPM) in conjunction with the function "Safe Torque Off" (p9601, p9801) (only for
synchronous motors).
When using a synchronous motor with VPM connected to a high-frequency converter, the following must apply:
p1082 [rpm] <= p0348 * (r0377 + p0233) / p0233
When a fault condition exists, the VPM short-circuits the motors. During the short-circuit, the pulses must be sup-
pressed - this means that the terminals for the function "Safe Torque Off" (STO) must be connected to the VPM.
When using a VPM, p0643 must be set to 1.
- activating the internal voltage protection (IVP) with p1231 = 3 (only for synchronous motors).
See also: p0643 (Overvoltage protection for synchronous motors), p1231 (Armature short-circuit / DC braking con-
figuration)
F07433 Drive: Closed-loop control with encoder is not possible as the encoder has not been
unparked
Message value: %1
Drive object: SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction: NONE (OFF1, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: The changeover to closed-loop control with encoder is not possible as the encoder has not been unparked.
Remedy: - check whether the encoder firmware supports the "parking" function (r0481.6 = 1).
- upgrade the firmware.