Description: The ramp-function generator ramps-down the speed setpoint from the maximum speed (p1082) down to standstill
(setpoint = 0) in this time.
Further, the ramp-down time is always effective for OFF1.
Dependency: Refer to: p1082
Note: The following applies for SERVO:
The ramp-function generator is only available when the function module "extended setpoint channel" is active
(r0108.8 = 1).
Description: Sets the signal source for bypassing the ramp generator (ramp-up and ramp-down times = 0).
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: For VECTOR in encoderless operation, it is not permissible that the ramp-function generator is bypassed.
Description: Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Description: Sets the final rounding-off time for the extended ramp generator. The value applies to ramp-up and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
p1121[0...n] Ramp-function generator ramp-down time / RFG ramp-down time
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(1), U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: 3060, 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 999999.000 [s] 10.000 [s]
p1122[0...n] BI: Bypass ramp-function generator / Bypass RFG
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2505
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p1130[0...n] Ramp-function generator initial rounding-off time / RFG t_start_round
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1131[0...n] Ramp-function generator final rounding-off time / RFG t_end_delay
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]