Parameter
List of parameters
1-448
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
17: Data backup does not match parameterized encoder/motor
18: Data backup directory not permissible
19: Component already contains data
20: Component does not contain any data
21: Component is not an SMI or a DQI
22: SMI data cannot be downloaded for component
30: Delete SMI data
35: Confirmation of SMI data delete required
36: SMI data deleted and POWER ON required for component
37: Access level not sufficient for delete
38: Delete SMI data not permitted for component
Dependency: Refer to: p4690, p4692, p4693
Notice: Once SMI/DQI data has been deleted or downloaded successfully, the component has to be powered up.
Note: SMI: SINAMICS Sensor Module Integrated
DLQ encoder: DRIVE-CLiQ encoder
Help for error value = 11:
- Save the data for the original SMI on the memory card.
- Use an SMI with a suitable hardware version.
Help for error value = 12:
- Set the correct component number or connect the component.
Help for error value = 15:
- Check the DRIVE-CLiQ wiring for the component.
Help for error value = 16:
- Check the DRIVE-CLiQ wiring for the component.
Help for error value = 17:
- Save the data for the original SMI on the memory card.
Help for error value = 18:
- Set parameter p4693 to an appropriate value.
Help for error value = 19:
- Perform an SMI delete or use a blank SMI.
Help for error value = 20:
- Use an SMI card that is not blank.
Help for error value = 21:
- Set the correct component number (p4690).
Note for error value = 22:
- Data cannot be downloaded for component.
Help for error value = 35:
- Reset parameter p4691 to 30.
Help for error value = 37:
- Set the access level to Expert or higher.
Help for error value = 38:
- Set the correct component number (p4690 >= 200).
Description: Setting to back up the data of all SMIs and DQIs featured in the target topology.
Value: 0: Inactive
1: Save data of all SMIs and DQIs
10: Save all data successful
13: Insufficient memory space for backup
p4692 SMI spare part save data of all SMIs / Save SMI data
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 29 0