List of faults and alarms
Faults and alarms
3-1003
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Remedy: - delete the drive belonging to this component in the commissioning software project and download the new config-
uration to the drive unit.
- re-configure the drive belonging to this component in the commissioning software project and download the new
configuration to the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check the 24 V supply voltage.
- check that the component is working properly.
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics capa-
bility (e.g. setpoint/actual value comparison).
A01487 Topology: Comparison option slot components missing in the actual topology
Message value: Component number: %1
Drive object: CU_S110-CAN, CU_S110-DP, CU_S110-PN
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected an option slot module in the target topology that is not available in the actual
topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Remedy: - delete the option board in the commissioning software project and download the new configuration to the drive unit.
- re-configure the drive unit in the commissioning software project and download the new configuration to the drive
unit.
- check that the actual topology matches the target topology and if required, change over.
- check that the option board is functioning correctly
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics capa-
bility (e.g. setpoint/actual value comparison).
A01488 Topology: Comparison EnDat encoder missing in the actual topology
Message value: Component number: %1
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected an EnDat encoder in the target topology that is not available in the actual
topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Remedy: - re-configure the drive belonging to the encoder in the commissioning software project (encoder configuration) and
download the new configuration to the drive unit.
- delete the drive belonging to the encoder in the commissioning software project and download the new configura-
tion to the drive unit.
- check that the actual topology matches the target topology and if required, change over.
Note:
Under "Topology --> Topology view" the commissioning software where relevant offers improved diagnostics capa-
bility (e.g. setpoint/actual value comparison).
A01489 Topology: Comparison motor with DRIVE-CLiQ missing in the actual topology
Message value: Component number: %1
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected a motor with DRIVE-CLiQ in the target topology that is not available in the
actual topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.