Parameter
List of parameters
1-406
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
BI: p2661 = 1 signal
The measured value received via CI: p2660 is valid.
BI: p2661 = 0 signal
The measured value received via CI: p2660 is invalid.
Dependency: Refer to: r2526, p2660
Description: Sets the signal source for the feedback signal "adjustment value valid".
BI: p2662 = 1 signal
The adjustment value received via CI: p2660 is valid.
BI: p2662 = 0 signal
The adjustment value received via CI: p2660 is not valid.
Dependency: Refer to: r2526, p2660
Description: Sets the signal source for the feedback signal "clamping active for travel to fixed stop".
BI: p2663 = 1 signal
Clamping is active
BI: p2663 = 0 signal
Clamping is not active.
Dependency: Refer to: r2526
Note: The feedback signal from "terminals active" is, for the factory setting, dependent on the signal BO: r2526.8 (termi-
nals active when moving to a fixed stop).
Description: Displays the current absolute position setpoint.
Dependency: Refer to: p2530
Note: As standard, the following BICO interconnection is established: CI: p2530 = r2665
p2662 BI: EPOS adjustment value valid feedback signal / Adj val valid FS
SERVO_S110-CAN
(EPOS),
SERVO_S110-DP
(EPOS),
SERVO_S110-PN
(EPOS)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: Basic positioner Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 2526.9
p2663 BI: EPOS clamping active feedback signal / Clamping active FS
SERVO_S110-CAN
(EPOS),
SERVO_S110-DP
(EPOS),
SERVO_S110-PN
(EPOS)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 3616
P-Group: Basic positioner Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 2526.8
r2665 CO: EPOS position setpoint / s_set
SERVO_S110-CAN
(EPOS),
SERVO_S110-DP
(EPOS),
SERVO_S110-PN
(EPOS)
Can be changed: - Calculated: - Access level: 1
Data type: Integer32 Dynamic index: - Func. diagram: 3635
P-Group: Basic positioner Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [LU] - [LU] - [LU]