EasyManua.ls Logo

Siemens SINAMICS S110 - Fig. 2-92 3010 - Fixed speed setpoints

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function diagrams
Setpoint channel
2-854
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Fig. 2-92 3010 – Fixed speed setpoints
- 3010 -
Function diagram
87654321
fp_3010_98_eng.vsd
DO: SERVO
SINAMICS S110
30.09.11 V04.04.00
Setpoint channel - Fixed speed setpoints
r1024
Fixed speed setpoint, actual
0 0 1 1
0 1 0 1
0 1 1 0
0 1 1 1
1 0 0 1
1 0 1 0
1 0 1 1
1 1 0 0
1 1 0 1
1 1 1 0
1 1 1 1
0 0 0 1
0 0 1 0
Fixed speed setpoint 1
-210 000.000...210 000.000 [rpm]
p1001[D] (0.000)
Fixed speed setpoint 2
-210 000.000...210 000.000 [rpm]
p1002[D] (0.000)
Fixed speed setpoint 3
-210 000.000...210 000.000 [rpm]
p1003[D] (0.000)
Fixed speed setpoint 4
-210 000.000...210 000.000 [rpm]
p1004[D] (0.000)
Fixed speed setpoint 5
-210 000.000...210 000.000 [rpm]
p1005[D] (0.000)
Fixed speed setpoint 6
-210 000.000...210 000.000 [rpm]
p1006[D] (0.000)
Fixed speed setpoint 7
-210 000.000...210 000.000 [rpm]
p1007[D] (0.000)
Fixed speed setpoint 8
-210 000.000...210 000.000 [rpm]
p1008[D] (0.000)
Fixed speed setpoint 9
-210 000.000...210 000.000 [rpm]
p1009[D] (0.000)
Fixed speed setpoint 10
-210 000.000...210 000.000 [rpm]
p1010[D] (0.000)
Fixed speed setpoint 11
-210 000.000...210 000.000 [rpm]
p1011[D] (0.000)
Fixed speed setpoint 12
-210 000.000...210 000.000 [rpm]
p1012[D] (0.000)
Fixed speed setpoint 13
-210 000.000...210 000.000 [rpm]
p1013[D] (0.000)
Fixed speed setpoint 14
-210 000.000...210 000.000 [rpm]
p1014[D] (0.000)
Fixed speed setpoint 15
-210 000.000...210 000.000 [rpm]
p1015[D] (0.000)
p1001[D]
p1003[D]
p1002[D]
p1004[D]
p1005[D]
p1006[D]
p1007[D]
p1008[D]
p1009[D]
p1010[D]
p1011[D]
p1012[D]
p1013[D]
p1014[D]
0.000
Fixed speed setpoint number actual
0...15
r1197
<100>
Fixed speed setpoint selection bit 0
r1198.0
Fixed speed setpoint selection bit 1
r1198.1
Fixed speed setpoint selection bit 2
r1198.2
Fixed speed setpoint selection bit 3
r1198.3
From
control word
setpoint
channel
0 0 0 0
0 1 0 0
1 0 0 0
[2505.3]
p1020
[2505.3]
p1021
[2505.3]
p1022
[2505.3]
p1023
Refer to [1020.7]
4000.00 μs
<100> For SERVO, the following applies:
Only if the function module "extended setpoint
channel" is activated (r0108.8 = 1).

Table of Contents