Siemens SINAMICS S110 - p0607[0...n] Temperature sensor fault timer; Sensor fault time; p0611[0...n] I2 t motor model thermal time constant; I2 t mot_mod T; p0612[0...n] Thermal motor model configuration; Therm Mot_mod conf

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameter
1-135
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Note: With p0606 = 0 s, the timer is de-activated and only the fault threshold is effective.
KTY sensor: When setting the minimum value, the timer is disabled and a fault is not output until p0605 is
exceeded.
PTC sensor, bimetallic NC contact: The timer minimum value has no special significance.
Description: Sets the timer between the output of alarm and fault for a temperature sensor fault.
If there is a sensor fault, this timer is started. If the sensor fault is still present after the timer has expired, a corre-
sponding fault message is output.
Notice: The parameterized time is internally rounded-off to an integer multiple of 48 ms.
Note: If the motor is an induction motor, the timer is switched off when setting the minimum value and no alarm is output.
Temperature monitoring is then based on the thermal model.
Description: Sets the winding time constant.
The time constant specifies the warm-up time of the cold stator winding when loaded with the motor standstill cur-
rent up until a temperature rise of 63 % of the continuously permissible winding temperature has been reached.
Dependency: This parameter is only used for synchronous motors (p0300 = 2xx).
Refer to: r0034, p0612, p0615
Refer to: F07011, A07012, A07910
Caution: This parameter is automatically pre-set from the motor database for motors from the motor list (p0301).
When selecting a catalog motor, this parameter cannot be changed (write protection). Information in p0300 should
be carefully observed when removing write protection.
Note: When parameter p0611 is reset to 0, then this switches out the thermal I2t motor model (also refer to p0612).
If no temperature sensor is parameterized, then the ambient temperature for the thermal motor model is referred to
p0625.
Description: Sets the configuration for the thermal motor model.
Dependency: Refer to: r0034, p0611, p0615
p0607[0...n] Temperature sensor fault timer / Sensor fault time
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 600.000 [s] 0.100 [s]
p0611[0...n] I2t motor model thermal time constant / I2t mot_mod T
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
0 [s] 20000 [s] 0 [s]
p0612[0...n] Thermal motor model configuration / Therm Mot_mod conf
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: MDS, p0130 Func. diagram: 8017
P-Group: - Units group: - Unit selection: -
Not for motor type: REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
- - 0010 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Activate I2t motor model Yes No -
01 Activate motor temperature model Yes No -