List of parameters
Parameter
1-201
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
For synchronous motors, the following additionally applies:
In the automatic calculation (p0340 = 1), p1082 is limited to speeds for which the rated current of the power unit (S1
continuous operation r0207[3]) is not sufficient as field current: p1082 < p0348 / (1 - r0207 / r0331), valid for
r0207[3]<r0331.
On the other hand, an additional limit is effective, which prevents the EMF from exceeding the maximum DC link
voltage (see p0643 and p1231).
The effective assignment of the motor data set parameter (e.g. p0311) to the drive data set parameter p1082 when
pre-assigning should be taken from p0186.
p1082 is also available in the quick commissioning (p0010 = 1); this means that when exiting via p3900 > 0, the
value is not changed.
Description: Sets the maximum speed for the positive direction.
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Description: Displays the effective positive speed limit.
Dependency: Refer to: p1082, p1083, p1085
Description: Sets the signal source for the speed limit of the positive direction.
Description: Sets the speed limit for the negative direction.
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p1083[0...n] CO: Speed limit in positive direction of rotation / n_limit pos
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: 3050, 3095
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 210000.000 [rpm]
r1084 CO: Speed limit positive effective / n_limit pos eff
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 3050, 3095
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1085[0...n] CI: Speed limit in positive direction of rotation / n_limit pos
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 3050
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 1083[0]
p1086[0...n] CO: Speed limit in negative direction of rotation / n_limit neg
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: 3050, 3095
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
-210000.000 [rpm] 0.000 [rpm] -210000.000 [rpm]