Description: Sets the filter time for the SSM feedback signal to detect standstill.
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: The filter time is effective only if the function is enabled (p9301.16 = p9501.16 = 1).
The parameter is included in the crosswise data comparison of the two monitoring channels.
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Description: Sets the velocity limit for the SSM feedback signal to detect standstill (n < nx).
When this limit value is undershot, the signal "SSM feedback signal active" is set.
For p9368 = p9568 = 0 the value in p9346/p9546 is also applicable for the function "SAM".
Dependency: Refer to: p9546
Caution: The "SAM" function is switched out if the selected threshold value is undershot.
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
Description: Sets the velocity limit for the SSM feedback signal to detect standstill (n < nx).
When this limit value is undershot, the signal "SSM feedback signal active" is set.
For p9368 = p9568 = 0 the value in p9346/p9546 is also applicable for the function "SAM".
Dependency: Refer to: p9546
Caution: The "SAM" function is switched out if the selected threshold value is undershot.
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: SAM: Safe Acceleration Monitor (safe acceleration monitoring)
SSM: Safe Speed Monitor (safety-relevant feedback signal from the velocity monitoring)
p9345 SI Motion SSM filter time (processor 2) / SI Mtn SSM filt P2
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 2860
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [µs] 100000.00 [µs] 0.00 [µs]
p9346 SI Motion SSM velocity limit (processor 2) / SI Mtn SSM v_limP2
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 2860
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [mm/min] 1000000.00 [mm/min] 20.00 [mm/min]
p9346 SI Motion SSM velocity limit (processor 2) / SI Mtn SSM v_limP2
SERVO_S110-CAN
(Safety rot),
SERVO_S110-DP
(Safety rot),
SERVO_S110-PN
(Safety rot)
Can be changed: C2(95) Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 2860
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 1000000.00 [rpm] 20.00 [rpm]