List of parameters
Parameter
1-97
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Selects the encoder from the list of encoder types that the OEM supports.
Note: The connected encoder can be identified by p0400 = 10000. This means that the encoder must support this and is
possible in the following cases: Motor with DRIVE-CLiQ, encoder with EnDat interface.
If an identification is not possible, then p0400 is set to 0.
The encoder data (e.g. pulse number p0408) can only be changed when p0400 = 9999.
Using p0400 = 20000, the encoder type can be selected from the list of OEM encoders using p0401.
Description: Settings for the basic encoder properties.
Caution: This parameter is automatically pre-set for encoders from the encoder list (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400
should be carefully observed when removing write protection.
Notice: If an SSI encoder (bit 9 = 1) is used as motor encoder for permanent-magnet synchronous motors, then this is only
permissible in conjunction with an additional A/B track (bit 3 = 1 or bit 4 = 1).
Note: ZM: Zero mark
SMC: Sensor Module Cabinet
If a technique to determine the commutation information/data has not been selected (e.g. track C/D, Hall sensor),
and the encoder pulse number is an integer multiple of the pole number, then the following applies:
The track A/B is adjusted to match the magnetic position of the motor.
p0401[0...n] Encoder type, OEM selection / Enc type OEM sel
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(1, 4) Calculated: - Access level: 2
Data type: Integer16 Dynamic index: EDS, p0140 Func. diagram: 1580, 4704
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 32767 0
p0404[0...n] Encoder configuration effective / Enc_config eff
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: EDS, p0140 Func. diagram: 4010, 4704
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 0000
0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Linear encoder Yes No -
01 Abs value encoder Yes No -
02 Multiturn encoder Yes No -
03 Track A/B sq-wave Yes No -
04 Track A/B sinus Yes No -
05 Track C/D Yes No -
06 Hall sensor Yes No -
08 EnDat encoder Yes No -
09 SSI encoder Yes No -
10 DRIVE-CLiQ encoder Yes No -
11 Digital encoder Yes No -
12 Equidistant zero mark Yes No -
13 Irregular zero mark Yes No -
14 Distance-coded zero mark Yes No -
15 Commutation with zero mark (not ASM) Yes No -
16 Acceleration Yes No -
17 Track A/B analog Yes No -
20 Voltage level 5 V Yes No -
21 Voltage level 24 V Yes No -
22 Remote sense (only SMC30) Yes No -
23 Resolver excit. Yes No -