Parameter
List of parameters
1-30
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
200: Wait for booting/partial booting
250: Device signals a topology error
Dependency: Refer to: r0046
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
Note: OC: Operating condition
EP: Enable Pulses (pulse enable)
RFG: Ramp-function generator
COMM: Commissioning
MotID: Motor data identification
SS2: Safe Stop 2
SOS: Safe Operating Stop
STO: Safe Torque Off
Description: Sets the access level for reading and writing parameters via the Basic Operator Panel (BOP).
Value: 1: Standard
2: Extended
3: Expert
4: Service
Note: Access level 0 (user-defined):
Parameters from the user-defined list (p0013). Not used as of firmware version 2.6 (p0016).
Access level 1 (standard):
Parameters for the simplest operator control possibility (e.g. p1120 = ramp-function generator, ramp-up time).
Access level 2 (extended):
Parameters to operate the basic functions of the drive unit.
Access level 3 (experts):
Expert know-how is required for these parameters (e.g. BICO parameterization).
Access level 4 (service):
For these parameters, it is necessary that authorized service personnel enter the appropriate password (p3950).
Description: Sets the parameter number and parameter index for display for p0006 = 2, 4 for the Basic Operator Panel (BOP).
Examples for the SERVO drive object:
p0005[0] = 21, p0005[1] = 0: Actual speed smoothed (r0021)
p0005[0] = 25, p0005[1] = 0: Output voltage smoothed (r0025)
Index: [0] = Parameter number
[1] = Parameter index
Dependency: Refer to: p0006
p0003 BOP access level / BOP acc_level
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: C1, U, T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 4 1
p0005[0...1] BOP operating display selection / BOP op_disp sel
All objects Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 [0] 2
[1] 0