Description: Displays the motor code number from the saved motor data from a motor with DRIVE-CLiQ.
Note: Drive commissioning can only be exited if the code number that was downloaded (r0302) matches the stored code
number (p0301). If the numbers differ, then the motor data set should be re-loaded using p0300 = 10000.
The motor data are always expected from the first encoder that is assigned to the drive data sets (refer to p0187 =
encoder 1) data set number.
The value is not updated cyclically but only on specific events (e.g. update DRIVE-CLiQ device).
r0302 = 0: No motor with DRIVE-CLiQ found
Description: Displays the status word of the automatic motor parameter sensing of a motor with DRIVE-CLiQ.
Motor parameter sensing takes place in the following events if the SMI is connected to the Motor Module and the
encoder is activated (p0145):
- Warm restart
- downloading projects.
- POWER ON (off/on).
- where p0300 = 10000, 10001.
Dependency: Refer to: p0145, p0300
Note: SMI: SINAMICS Sensor Module Integrated
Description: Sets the rated motor voltage (rating plate).
Dependency: Refer to: p0349
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
r0302[0...n] Motor code number of motor with DRIVE-CLiQ / Motor code Mot DLQ
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r0303[0...n] Motor with DRIVE-CLiQ status word / Motor w DLQ ZSW
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor data set selected MDS1 MDS0 -
01 Motor connection type Delta Star -
02 Windings can be changed Yes No -
03 Windings can be changed number 2 0 -
p0304[0...n] Rated motor voltage / Mot U_rated
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: 6300, 6724
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [Vrms] 20000 [Vrms] 0 [Vrms]