EasyManua.ls Logo

Siemens SINAMICS S110 - p0601[0...n] Motor temperature sensor type; Mot_temp_sens type; p0603 CI: Motor temperature signal source; Mot temp S_src

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameter
1-133
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Dependency: Refer to: r0458, p0601, p0603
Caution: If, for a selected temperature sensor (p0600 > 0), the motor temperature sensor is not connected but another
encoder, then the temperature adaptation of the motor resistances must be switched out. Otherwise, in controlled-
loop operation, torque errors will occur that will mean that the drive will not be able to be stopped.
Notice: The parameter is calculated in the drive using p0340 and is inhibited for p0340 > 0.
Note: Re p0600 = 0:
With induction motors, the motor temperature is calculated using the motor temperature model (see also p0612, bit
1).
Re p0600 = 10:
The BICO interconnection should be executed via connector input CI: p0603.
Re p0600 = 11:
For SINAMICS S120 AC Drive (AC/AC) and using the Control Unit Adapter CUA31, the temperature sensor is con-
nected at the adapter (X210).
Description: Sets the sensor type for the motor temperature monitoring.
Value: 0: No sensor
1: PTC alarm & timer
2: KTY84
3: KTY84 and PTC (only for motors with DRIVE-CLiQ):
Dependency: The thermal motor model is only calculated for p0612.1 = 1.
Refer to: r0458, p0600, p0612
Note: The temperature sensor for the temperature evaluation is set in p0600.
For p0600 = 10 (temperature sensor via a BICO interconnection), the setting in p0601 has no significance.
Information on using temperature sensors is provided in the following literature:
- hardware description of the appropriate components
- SINAMICS S120 Commissioning Manual
Re p0601 = 1 (PTC alarm & timer):
Tripping resistance = 1650 Ohm.
After the tripping resistance has been exceeded, an appropriate alarm is output and after the delay time set in
p0606 has expired, an appropriate fault is output.
Re p0601 = 3 (KTY84 and PTC (only for motors with DRIVE-CLiQ)):
For motors with DRIVE-CLiQ and 2 temperature sensors, the value is automatically set.
Description: Sets the signal source to evaluate the motor temperature via a BICO interconnection.
Dependency: Refer to: p0600
Note: Temperature sensor KTY: Valid temperature range -48 °C ... 248 °C.
PTC temperature sensor:
For a value = -50 °C, the following applies: Motor temperature < nominal response temperature of the PTC.
For a value = 250 °C, the following applies: Motor temperature >= nominal response temperature of the PTC.
p0601[0...n] Motor temperature sensor type / Mot_temp_sens type
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 2
p0603 CI: Motor temperature signal source / Mot temp S_src
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(3), T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dynamic index: - Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: p2006 Expert list: 1
Min Max Factory setting
- - 0

Table of Contents

Other manuals for Siemens SINAMICS S110

Related product manuals