Siemens SINAMICS S110 - p0922 IF1 PROFIdrive telegram selection; IF1 PD Telegr_sel

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter
List of parameters
1-176
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Note: Permissible PROFIBUS addresses: 1 ... 126
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
Description: Sets the send and receive telegram.
Value: 390: SIEMENS telegram 390, PZD-2/2
391: SIEMENS telegram 391, PZD-3/7
392: SIEMENS telegram 392, PZD-3/15
393: SIEMENS telegram 393, PZD-4/21
394: SIEMENS telegram 394, PZD-3/3
999: Free telegram configuration with BICO
Description: Sets the send and receive telegram.
Value: 1: Standard telegram 1, PZD-2/2
2: Standard telegram 2, PZD-4/4
3: Standard telegram 3, PZD-5/9
4: Standard telegram 4, PZD-6/14
102: SIEMENS telegram 102, PZD-6/10
103: SIEMENS telegram 103, PZD-7/15
999: Free telegram configuration with BICO
Dependency: Refer to: p2038
Refer to: F01505, F01506
Note: For p0922 = 100 ... 199, p2038 is automatically set to 1 and p2038 can no longer be changed. This means that for
these telegrams, the "SIMODRIVE 611 universal" interface mode is set and cannot be changed.
If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
Description: Sets the send and receive telegram.
Value: 7: Standard telegram 7, PZD-2/2
9: Standard telegram 9, PZD-10/5
110: SIEMENS telegram 110, PZD-12/7
p0922 IF1 PROFIdrive telegram selection / IF1 PD Telegr_sel
CU_S110-DP,
CU_S110-PN
Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2420,
2422, 2424
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
390 999 999
p0922 IF1 PROFIdrive telegram selection / IF1 PD Telegr_sel
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2420,
2422, 2423, 2424
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 999 999
p0922 IF1 PROFIdrive telegram selection / IF1 PD Telegr_sel
SERVO_S110-DP
(EPOS, Pos ctrl),
SERVO_S110-PN
(EPOS, Pos ctrl)
Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2420,
2422, 2423, 2424
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
7 999 999