List of parameters
Parameter
1-153
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: The scaling characteristic for the test sockets is defined using two points. This parameter specifies the y coordinate
(output voltage) of the first point on the characteristic.
Index: [0] = T0
[1] = T1
[2] = Reserved
Dependency: Can only be set when p0776 = 99.
Refer to: p0777, p0779, p0780, r0786
Description: The scaling characteristic for the test sockets is defined using two points. This parameter specifies the x coordinate
(percentage) of the second point on the characteristic.
Index: [0] = T0
[1] = T1
[2] = Reserved
Dependency: Can only be set when p0776 = 99.
Refer to: p0777, p0778, p0780, r0786
Note: The value 100.00 % corresponds to 4.98 V.
Description: The scaling characteristic for the test sockets is defined using two points. This parameter specifies the y coordinate
(output voltage) of the second point on the characteristic.
Index: [0] = T0
[1] = T1
[2] = Reserved
Dependency: Can only be set when p0776 = 99.
Refer to: p0777, p0778, p0779, r0786
p0778[0...2] Test socket characteristic value y1 / Test skt char y1
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 8134
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [V] 4.98 [V] 2.49 [V]
p0779[0...2] Test socket characteristic value x2 / Test skt char x2
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 8134
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-100000.00 [%] 427.9E9 [%] 100.00 [%]
p0780[0...2] Test socket characteristic value y2 / Test skt char y2
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 8134
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [V] 4.98 [V] 4.98 [V]