Parameter
List of parameters
1-218
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Note: Index 0:
The monitoring time starts when the faults are detected. If the automatic acknowledgements are not successful, the
monitoring time runs again. If, after the monitoring time has expired, the drive has still not successfully started again
(flying restart and magnetizing of the motor must have been completed: r0056.4 = 1), then fault F07320 is output.
The monitoring is de-activated with p1213 = 0. If p1213 is set lower than the sum of p1212, the magnetizing time
p0346 and the additional delay time due to the flying restart, then fault F07320 is generated at each restart. If, for
p1210 = 1, the time in p1213 is set lower than in p1212, then fault F07320 is also generated at each restart.
The monitoring time must be extended if the faults that occur cannot be immediately and successfully acknowl-
edged (e.g. for faults that are permanently present).
In the case of p1210 = 14, 16, the faults which are present must be acknowledged manually within the time in
p1213 index 0. Otherwise, fault F07320 is generated after the set time.
Index 1:
The start counter (refer to r1214) is only set back to the starting value p1211 if, after successful restart, the time in
p1213 index 1 has expired. The delay time is not effective for fault acknowledgement without automatic restart
(p1210 = 1). After a power failure (blackout) the delay time only starts after the line supply returns and the Control
Unit boots. The start counter is set to p1211, if F07320 occurred, the power-on command is withdrawn and the fault
is acknowledged.
The start counter is immediately updated if the starting value p1211 or the mode p1210 is changed.
Description: Displays the status of the automatic restart (AR).
Note: Re bit 00:
State to display the single initialization after POWER ON.
Re bit 01:
State in which the automatic restart function waits for faults (initial state).
Re bit 02:
General display that a fault has been identified and that the restart or acknowledgement has been initiated.
Re bit 03:
Displays the acknowledge command within the "acknowledge alarms" state (bit 4 = 1). For bit 5 = 1 or bit 6 = 1, the
acknowledge command is continually displayed.
Re bit 04:
State in which the faults that are present are acknowledged. The state is exited again after successful acknowl-
edgement. A change is only made into the next state if it is signaled that a fault is no longer present after an
acknowledgement command (bit 3 = 1).
Re bit 05:
State in which the drive is automatically powered up (only for p1210 = 4, 6).
r1214.0...15 CO/BO: Automatic restart, status / AR status
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Initialization Yes No -
01 Wait for alarm Yes No -
02 Auto restart act Yes No -
03 Setting the acknowledgement command Yes No -
04 Acknowledge alarms Yes No -
05 Restart Yes No -
06 Delay time running after automatic power-
up
Yes No -
07 Fault Yes No -
10 Effective fault Yes No -
12 Start count. bit 0 ON OFF -
13 Start count. bit 1 ON OFF -
14 Start count. bit 2 ON OFF -
15 Start count. bit 3 ON OFF -