Function diagrams
Free function blocks (FBLOCKS)
2-932
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Fig. 2-163 7270 – LVM (double-sided limit monitor with hysteresis)
- 7270 -
Function diagram
87654321
fp_7270_98_eng.vsd
DO: All Objects
SINAMICS S110
20.04.09 V04.04.00
FBLOCKS - LVM (limit value monitor, double-sided with hysteresis)
LVM 0 input quantity above interval QU
r20270
LVM 0 run-time group
p20273 (9999)
LVM 0 input quantity within interval QM
r20271
LVM 0 input quantity below interval QL
r20272
LVM 0
interval average value M
p20267
LVM 0 interval limit L
p20268
LVM 0
hysteresis HY
p20269
LVM 0 run sequence
p20274 (720)
QM
QU
QL
M-L M+L
HY HY
L
L
0
1
M
ML HY
0
1
0
1
LVM 1 input quantity above interval QU
r20279
LVM 1 run-time group
p20282 (9999)
LVM 1 input quantity within interval QM
r20280
LVM 1 input quantity below interval QL
r20281
LVM 1
interval average value M
p20276
LVM 1 interval limit L
p20277
LVM 1
hysteresis HY
p20278
LVM 1 run sequence
p20283 (730)
QL
ML HY
QM
QU
M-L M+L
HY HY
L
L
0
1
M
0
1
0
1
LVM 0 input X
(0)
p20266
X X
LVM 1 input X
(0)
p20275
LVM 1LVM 0
Complex function blocks