Siemens SINAMICS S110 - p1455[0...n] CI: Speed controller P gain adaptation signal; n_ctrl Adpt_sig Kp; p1456[0...n] Speed controller P gain adaptation lower starting point; n_ctrl AdaptKpLow; p1457[0...n] Speed controller P gain adaptation upper starting point; n_ctrl AdaptKp up; p1458[0...n] Adaptation factor, lower; Adapt_factor lower

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter
List of parameters
1-244
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the source for the adaptation signal to additionally adapt the P gain of the speed controller.
Dependency: Refer to: p1456, p1457, p1458, p1459
Description: Sets the lower starting point of the adaptation range for the additional adaptation of the P gain of the speed control-
ler.
The values are in % and refer to the set source of the adaptation signal.
Dependency: Refer to: p1455, p1457, p1458, p1459
Description: Sets the upper starting point of the adaptation range for the additional adaptation of the P gain of the speed control-
ler.
The values are in % and refer to the set source of the adaptation signal.
Dependency: Refer to: p1455, p1456, p1458, p1459
Description: Sets the adaptation factor before the adaptation range (0 % ... p1456) to additionally adapt the P gain of the
speed/velocity controller.
Dependency: Refer to: p1455, p1456, p1457, p1459
p1455[0...n] CI: Speed controller P gain adaptation signal / n_ctrl Adpt_sig Kp
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 5050
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0
p1456[0...n] Speed controller P gain adaptation lower starting point / n_ctrl AdaptKpLow
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: 5050
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 400.00 [%] 0.00 [%]
p1457[0...n] Speed controller P gain adaptation upper starting point / n_ctrl AdaptKp up
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: 5050
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 400.00 [%] 0.00 [%]
p1458[0...n] Adaptation factor, lower / Adapt_factor lower
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: 5050
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [%] 200000.0 [%] 100.0 [%]