Fig. 2-169 8011 – Speed signals 2
- 8011 -
Function diagram
87654321
fp_8011_98_eng.vsd
DO: SERVO
SINAMICS S110
30.09.11 V04.04.00
Signals and monitoring functions - Speed signals 2
–
Ramp-up/ramp-down completed
r2199.5
[2537.3]
+
SET
(Q=1)
RESET
(Q=0)
Q
Q
n_act 2
0
p2154[C]
4000.00 μs
r2169
n_act smooth signal
[8010.2]
[8012.5]
[8013.1]
0
1
n_hysteresis 3
0.00...300.00 rpm
p2150[D] (2.00)
n_act 0
r2197.3 [2534.3]
0
n_set for msg
r1170
p2151[C]
<2>
[3080.8]
n_thresh val 4
0.00...210.000 rpm
p2163[D] (90.00)
n_hysteresis 4
0.00...200.00 rpm
p2164[D] (2.00)
0
1
0
1
0
0
1
n_hysteresis 3
0.00...300.00 rpm
p2150[D] (2.00)
n_hysteresis 3
0.00...300.00 rpm
p2150[D] (2.00)
(0)
RFG active
p2148[C]
t_on n_act=n_set
0.0...10 000.0 ms
p2167[D] (200.0)
T0
1 = RESET
Priority
1 RESET
2 SET
[2537.3]
Speed setpoint actual value deviation in tolerance t_on
r2199.4
0T
t_del_off n_i=n_se
0.0...500.0 ms
p2166[D] (200.0)
Speed setpoint actual value deviation in tolerance t_off
r2197.7 [2534.3]
1
Torque control active
r1407.2
[6060.3]
Enable alarm A07903
p2149.0[D]
A07903 "Motor speed deviation"
1
0
1
A07903 is only signaled for p2149.0 = 1 and r2197.7 = 0.
n_thresh val 3
0.00...210000.00 rpm
p2161[D] (5.00)
n_set > 0
r2198.5 [2536.3]
|n_set|
p2161
r2198.4 [2536.3]
+
[5210.4]
n_set for msg
r1438
p2151[C]
<1>
<1> Applies only if the function module
"extended signals/monitoring functions" is active
(r0108.17 = 1).
<2> Evaluation only for:
Pulse enable and operating enable (r0899.2)
or OFF1
or OFF3
or rotating measurements
or friction characteristic plot.