List of parameters
Parameter
1-433
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the threshold value for the variable signaling function.
Description: Sets the hysteresis for the variable signaling function.
Description: Sets the pickup delay for the variable signaling function.
Notice: Values that do not comply with the following condition are treated just like value 0:
Pickup delay (p3297) >= sampling time (p3299)
Note: For a value of 0, the pickup delay is disabled.
The output signal is set if the condition for the 1 signal is fulfilled for longer than the selected time.
Description: Sets the dropout delay for the variable signaling function.
Notice: Values that do not comply with the following condition are treated just like value 0:
Dropout delay (p3298) >= sampling time (p3299)
Note: For a value of 0, the dropout delay is disabled.
The output signal is reset if the condition for the 0 signal is fulfilled for longer than the selected time.
p3295 Variable signaling function threshold value / Var sig thresh_val
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 5301
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-340.28235E36 340.28235E36 0.000
p3296 Variable signaling function hysteresis / Var sig hyst
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 5301
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 340.28235E36 0.000
p3297 Variable signaling function pickup delay / Var sig t_pickup
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 5301
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]
p3298 Variable signaling function dropout delay / Var sig t_dropout
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 5301
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 10000 [ms] 0 [ms]