List of parameters
Parameter
1-205
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Displays the speed/velocity setpoint after the changeover and limiting the direction.
Description: Sets the ramp-function generator type.
Value: 0: Basic ramp-function generator
1: Extended ramp-function generator
Note: Another ramp-function generator type can only be selected when the motor is at a standstill.
Description: Displays the setpoint at the input of the ramp-function generator.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: The setpoint is influenced by other functions, e.g. skip (suppressed) speeds, minimum and maximum limits.
Description: The ramp-function generator ramps-up the speed setpoint from standstill (setpoint = 0) up to the maximum speed
(p1082) in this time.
Dependency: Refer to: p1082
r1114 CO: Setpoint after the direction limiting / Setp after limit
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 1550, 3040,
3050
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1115 Ramp-function generator selection / RFG selection
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: 1550, 3080
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
r1119 CO: Ramp-function generator setpoint at the input / RFG setp at inp
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 1550, 1690,
3050, 3060, 3070
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1120[0...n] Ramp-function generator ramp-up time / RFG ramp-up time
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed: C2(1), U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: 3060, 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 999999.000 [s] 10.000 [s]