List of parameters
Parameter
1-639
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Bit 5 = SDI_pos_active
Bit 6 = SDI_neg_active
Note: Bit = 0 signal --> not selected
Bit = 1 signal --> selected
The selected signals (high-active) are OR'ed The result of the logic operation results in the status "Safe State".
Description: Sets the input mode for the safety digital inputs (F-DI).
Note: Only an NC contact can be connected for the safety digital inputs not listed.
Description: Sets the signal sources for F-DO 0 (X131.6).
The 6 signal sources in p10142[0...5] are AND'ed and the result is output at F-DO 0.
Value: 0: No function
1: STO active
2: SS1 active
3: SS2 active
4: SOS active
5: SLS active
6: SSM feedback signal active
7: Safe state
8: SOS selected
9: Internal event
10: Active SLS stage bit 0
11: Active SLS stage bit 1
12: SDI positive active
13: SDI negative active
Index: [0] = AND logic operation input 1
[1] = AND logic operation input 2
[2] = AND logic operation input 3
[3] = AND logic operation input 4
[4] = AND logic operation input 5
[5] = AND logic operation input 6
Bit field: Bit Signal name 1 signal 0 signal FP
00 Power_removed Selected Not selected -
01 SS1_active Selected Not selected -
02 SS2_active Selected Not selected -
03 SOS_active Selected Not selected -
04 SLS_active Selected Not selected -
05 SDI_pos_active Selected Not selected -
06 SDI_neg_active Selected Not selected -
p10140 SI F-DI input mode (processor 2) / SI F-DI mode P2
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 F-DI 1 (X130.2) NO contact NC contact 2850
01 F-DI 2 (X130.5) NO contact NC contact 2850
02 F-DI 3 (X131.2) NO contact NC contact 2850
p10142[0...5] SI F-DO 0 signal sources (processor 2) / SI F-DO 0 S_src P2
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: 2857
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 13 0