List of parameters
Parameter
1-227
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
If the contactor feedback signal (p1235) is parameterized, then the appropriate feedback signal (r1239.1) is
expected within this monitoring time after either opening or closing the contactor.
Dependency: Refer to: p1230, p1231, p1235, p1237, r1239
Refer to: A07904, F07905
Description: Sets the delay time when opening the contactor of the external armature short-circuit.
If no contactor feedback signal has been selected (p1235), then the system waits for this time before the pulses are
switched in.
Dependency: Refer to: p1230, p1231, p1235, p1236, r1239
Notice: This delay time must be at least long enough so that the contactor contacts reliably open before the pulses are
switched in. The delay time must be greater than the contactor response time. The Motor Module can be damaged
if the delay time is too short.
Description: Displays the state for the external armature short-circuit.
Value: 0: Switched off
1: Ready
2: Active
3: Active - feedback signal "Closed" OK
4: Active - feedback signal "Closed" missing
5: Prompt to remove the armature short-circuit
6: Active - feedback signal "Open" missing
Dependency: Refer to: p1230, p1231, p1235, p1236, p1237, r1239
Refer to: A07904, F07905
Note: Activation criterion (one of the following criteria is fulfilled):
- the signal at BI: p1230 (armature short-circuit activation) is 0.
- the drive is not in the state "S4: Operation" or in S5x (refer to function diagram 2610).
- the internal pulse enable is missing (r0046.19 = 0).
Re state "switched out" (r1238 = 0):
- the external armature short-circuit can be selected with p1231 = 1.
Re state "ready" (r1238 = 1):
- as soon as the activation criterion is fulfilled, then a transition is made into the state "active" (r1238 = 2).
Regarding the state "active" (r1238 = 2), "active - feedback signal "Closed" OK" (r1238 = 3)", "active - feedback sig-
nal "Closed" missing" (r1238 = 4)":
- the control signal to close contactor r1239.0 is set to "1" (closed) and the pulses are suppressed.
- if a contactor feedback signal is not connected (BI: p1235 = 0 signal), then a transition is immediately made into
state 3.
- if a contactor feedback signal is connected, then a transition is made into state 3 if the feedback signal at BI:
p1235 goes to "1" (closed) within the monitoring time (p1236).
- otherwise, a transition is made into state 4.
p1237[0...n] External armature short-circuit, delay time when opening / ASC ext t_wait
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 200 [ms]
r1238 CO: Armature short-circuit, external state / EASC state
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: 2610
P-Group: Functions Units group: - Unit selection: -
Not for motor type: ASM Scaling: - Expert list: 1
Min Max Factory setting
0 6 -