List of parameters
Parameter
1-67
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
115: PM250 (SINAMICS G120)
116: PM260 (SINAMICS G120)
118: SINAMICS G120 Px
120: PM340 (SINAMICS S120)
133: SINAMICS G120C
150: SINAMICS G
200: SINAMICS GM
250: SINAMICS SM
260: SINAMICS SM120
300: SINAMICS GL
350: SINAMICS SL
400: SINAMICS DCM
Note: For parallel circuit configurations, the parameter index is assigned to a power unit.
Description: Displays the properties supported by the power unit hardware.
Note: For parallel circuit configurations, the parameter index is assigned to a power unit.
Description: Displays the rated power unit power for various load duty cycles.
Index: [0] = Rating plate
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 cont duty cyc
[4] = S6 load duty cycle
Dependency: IECdrives (p0100 = 0): Units kW
NEMA drives (p0100 = 1): Units hp
Refer to: p0100
r0204[0...n] Power unit hardware properties / PU HW property
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: PDS Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Device type DC/AC device AC/AC device -
01 RFI filter available Yes No -
02 Active Line Module available Yes No -
03 Smart Line Module available Yes No -
04 Basic Line Module available with thyristor
bridge
Yes No -
05 Basic Line Module available with diode
bridge
Yes No -
06 Liquid cooling with cooling system (chassis
PU)
Yes No -
07 F3E regenerative feedback into the line sup-
ply
Yes No -
08 Internal Braking Module Yes No -
09 Different cooling type supported Yes No -
12 Safe Brake Control (SBC) supported No Yes -
13 Safety Integrated supported Yes No -
14 Internal LC output filter Yes No -
r0206[0...4] Rated power unit power / PU P_rated
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: -
P-Group: Converter Units group: 14_6 Unit selection: p0100
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [kW] - [kW] - [kW]