List of parameters
Parameter
1-175
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Displays the status word of the sequence control.
Note: Re bits 00, 01, 02, 04, 05, 06, 09:
For PROFIdrive, these signals are used for status word 1.
Re bit 13:
When the "Safe Brake Control" (SBC) is activated and selected, the brake is no longer controlled using this signal.
Re bit 14, 15:
These signals are only of significance when the "extended brake control" function module is activated (r0108.14 =
1).
Description: Displays or sets the PROFIBUS address for PROFIBUS interface on the Control Unit.
The address can be set as follows:
1) Using the DIP switch on the Control Unit.
--> p0918 can then only be read and displays the selected address.
--> A change only becomes effective after a POWER ON.
2) Using p0918
--> Only if all of the DIP switches are set to ON or OFF.
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
08 System time synchronized Yes No -
12 Slave sign-of-life bit 0 Yes No -
13 Slave sign-of-life bit 1 Yes No -
14 Slave sign-of-life bit 2 Yes No -
15 Slave sign-of-life bit 3 Yes No -
r0899.0...15 CO/BO: Status word sequence control / ZSW seq_ctrl
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1530, 2503
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Rdy for switch on Yes No -
01 Ready Yes No -
02 Operation enabled Yes No -
03 Jog active Yes No -
04 No coasting active OFF2 inactive OFF2 active -
05 No Quick Stop active OFF3 inactive OFF3 active -
06 Switching on inhibited active Yes No -
07 Drive ready Yes No -
08 Controller enable Yes No -
09 Control request Yes No -
11 Pulses enabled Yes No -
12 Open holding brake Yes No -
13 Command close holding brake Yes No -
14 Pulse enable from the brake control Yes No -
15 Setpoint enable from the brake control Yes No -
p0918 PROFIBUS address / PB address
CU_S110-DP Can be changed: T Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2410
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 126 126