Parameter
List of parameters
1-208
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Enables the ramp-function generator.
Dependency: Refer to: p1141, p1142
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for the command "continue ramp-function generator/freeze ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 5 (STW1.5).
BI: p1141 = 0 signal:
Freezes the ramp-function generator.
BI: p1141 = 1 signal:
Continues the ramp-function generator.
Dependency: Refer to: p1140, p1142
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The ramp-function generator is, independent of the state of the signal source, active in the following cases:
- OFF1/OFF3.
- ramp-function generator output within the suppression bandwidth.
- ramp-function generator output below the minimum speed.
Description: Sets the signal source for the command "enable setpoint/inhibit setpoint".
For the PROFIdrive profile, this command corresponds to control word 1 bit 6 (STW1.6).
p1140[0...n] BI: Enable ramp-function generator/inhibit ramp-function generator / RFG enable
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2501
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p1141[0...n] BI: Continue ramp-function generator/freeze ramp-function generator / Continue RFG
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2501
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p1142[0...n] BI: Enable setpoint/inhibit setpoint / Setpoint enable
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2501
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1