List of parameters
Parameter
1-293
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the sampling time for the process data communication (PZD).
Note: For clock cycle synchronous operation, the specified bus cycle time applies (Tdp).
Description: Connector output to interconnect PZD (setpoints) with word format received from the PROFIdrive controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
Note: IF1: Interface 1
Description: Connector output to interconnect PZD (setpoints) with word format received from the PROFIdrive controller.
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
[4] = PZD 5
[5] = PZD 6
[6] = PZD 7
[7] = PZD 8
[8] = PZD 9
[9] = PZD 10
[10] = PZD 11
[11] = PZD 12
[12] = PZD 13
[13] = PZD 14
[14] = PZD 15
[15] = PZD 16
[16] = PZD 17
[17] = PZD 18
[18] = PZD 19
[19] = PZD 20
Dependency: Refer to: r2060
p2048 PROFIdrive PZD sampling time / PZD t_sample
CU_S110-DP,
CU_S110-PN
Can be changed: C1(3) Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1.00 [ms] 16.00 [ms] 4.00 [ms]
r2050[0...4] CO: IF1 PROFIdrive PZD receive word / IF1 PZD recv word
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: 4000H Expert list: 1
Min Max Factory setting
- - -
r2050[0...19] CO: IF1 PROFIdrive PZD receive word / IF1 PZD recv word
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: 2440, 2468
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: 4000H Expert list: 1
Min Max Factory setting
- - -