Siemens SINAMICS S110 - p0615[0...n] I2 t motor model fault threshold; I2 t mot_mod thresh; p0616[0...n] Motor overtemperature alarm threshold 1; Mot temp alarm 1; p0620[0...n] Thermal adaptation, stator and rotor resistance; Mot therm_adapt R

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter
List of parameters
1-136
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Note: Re bit 00:
This bit is only used for permanent-magnet synchronous motors (p0300 = 2xx). It is only possible to switch in ther-
mal I2t monitoring with a time constant greater than zero (p0611 > 0).
Re bit 01:
This bit is used to activate/de-activate the thermal motor model for induction motors.
Description: Sets the fault threshold for monitoring using the thermal I2t motor model.
Dependency: The parameter is only used for permanent-magnet synchronous motors (p0300 = 2xx).
Refer to: r0034, p0611, p0612
Refer to: F07011, A07012
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Description: Sets the alarm threshold 1 for monitoring the motor temperature.
Note: The alarm threshold is not, as for p0604, coupled to the timer p0606. The hysteresis for canceling the fault is 2 Kel-
vin.
Description: Sets the thermal adaptation of the stator/primary section resistance and rotor/secondary section resistance accord-
ing to r0395 and r0396.
Value: 0: No thermal adaptation of stator and rotor resistances
1: Resistances adapted to the temperatures of the thermal model
2: Resistances adapted to the measured stator winding temperature
Note: For p0620 = 1, the following applies:
The stator resistance is adapted using the temperature in r0035 and the rotor resistance together with the model
temperature in r0633.
For p0620 = 2, the following applies:
The stator resistance is adapted using the temperature in r0035. If applicable, the rotor temperature for adapting
the rotor resistance is calculated from the stator temperature (r0035) as follows:
theta_R = (r0628 + r0625) / (r0627 + r0625) * r0035
p0615[0...n] I2t motor model fault threshold / I2t mot_mod thresh
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Units group: 21_1 Unit selection: p0505
Not for motor type: ASM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
0.0 [°C] 220.0 [°C] 180.0 [°C]
p0616[0...n] Motor overtemperature alarm threshold 1 / Mot temp alarm 1
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: 21_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [°C] 200.0 [°C] 195.0 [°C]
p0620[0...n] Thermal adaptation, stator and rotor resistance / Mot therm_adapt R
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 2