Parameter
List of parameters
1-368
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Note: The proportional gain is used define at which traversing velocity which following error is obtained (without pre-con-
trol)
Low proportional gain:
Slow response to a setpoint - actual value difference, the following error becomes large.
High proportional gain:
Fast response to the setpoint - actual value difference, the following error becomes small.
Description: Setting to activate the integral time of the position controller.
Value = 0 ms --> The I component of the position controller is de-activated.
Dependency: Refer to: p2538, r2559
Description: Sets the speed limit of the position controller output.
Dependency: Refer to: p2541
Description: Sets the signal source for the position controller output limit.
Dependency: Refer to: p2540
Description: Sets the standstill window for the standstill monitoring function.
After the standstill monitoring time expires, it is cyclically checked whether the difference between the setpoint and
actual position is located within the standstill window and, if required, an appropriate fault is output.
Value = 0 --> The standstill monitoring is de-activated.
p2539[0...n] LR integral time / Tn
SERVO_S110-CAN
(Pos ctrl),
SERVO_S110-DP
(Pos ctrl),
SERVO_S110-PN
(Pos ctrl)
Can be changed: U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: 4015
P-Group: Closed loop position control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [ms] 100000.00 [ms] 0.00 [ms]
p2540 CO: LR position controller output, speed limit / LR_outp limit
SERVO_S110-CAN
(Pos ctrl),
SERVO_S110-DP
(Pos ctrl),
SERVO_S110-PN
(Pos ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 4015
P-Group: Closed loop position control Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 210000.000 [rpm]
p2541 CI: LR position controller output, speed limit signal source / LR_outp lim S_src
SERVO_S110-CAN
(Pos ctrl),
SERVO_S110-DP
(Pos ctrl),
SERVO_S110-PN
(Pos ctrl)
Can be changed: T Calculated: - Access level: 1
Data type: Unsigned32 / FloatingPoint32 Dynamic index: - Func. diagram: 4015
P-Group: Closed loop position control Units group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 2540[0]
p2542 LR standstill window / Standstill window
SERVO_S110-CAN
(Pos ctrl),
SERVO_S110-DP
(Pos ctrl),
SERVO_S110-PN
(Pos ctrl)
Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: - Func. diagram: 4020
P-Group: Closed loop position control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [LU] 2147483647 [LU] 200 [LU]