List of parameters
Parameter
1-355
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the assigned encoder.
The actual value preprocessing and the closed-loop position control are carried out using the assigned encoder.
Value: 0: No encoder
1: Encoder 1
2: Encoder 2
Dependency: Refer to: p0187, p0188
Notice: For the setting p2502 = 0 (no encoder), closed-loop position control is not possible. This setting is only practical as
supportive measure to implement encoderless closed-loop speed control (e.g. if the motor encoder is defective).
Note: The assigned encoder (p2502 = 1, 2) must be allocated an encoder data set (p0187, p0188).
Description: Sets the neutral length units LU per 10 mm.
Therefore, for a linear scale, a reference is established between the physical arrangement and the neutral length
units LU used in the drive.
Example:
Linear scale, 10 mm should be broken down to units of µm (i.e. 1 LU = 1 µm).
--> p2503 = 10000
Note: The assignment to the grid spacing can be achieved using this for a rotary axis with linear encoder.
Description: Sets the motor revolutions for the gearbox factor between the motor shaft and load shaft.
Gearbox factor = motor revolutions (p2504) / load revolutions (p2505)
Dependency: Refer to: p0432, p0433, p2505
Note: The gearbox factor between the encoder shaft and the motor shaft is set using p0432 and p0433.
08 Technology controller actual value at the
minimum
Yes No -
09 Technology controller actual value at the
maximum
Yes No -
10 Technology controller output at the mini-
mum
Yes No -
11 Technology controller output at the maxi-
mum
Yes No -
p2502[0...n] LR encoder assignment / Encoder assignment
SERVO_S110-CAN
(Pos ctrl),
SERVO_S110-DP
(Pos ctrl),
SERVO_S110-PN
(Pos ctrl)
Can be changed: C2(25) Calculated: - Access level: 1
Data type: Integer16 Dynamic index: DDS, p0180 Func. diagram: 4010
P-Group: Closed loop position control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 1
p2503[0...n] LR length unit LU per 10 mm / LU per 10 mm
SERVO_S110-CAN
(Pos ctrl),
SERVO_S110-DP
(Pos ctrl),
SERVO_S110-PN
(Pos ctrl)
Can be changed: C2(25) Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: DDS, p0180 Func. diagram: 4010
P-Group: Closed loop position control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 [LU] 2147483647 [LU] 10000 [LU]
p2504[0...n] LR motor/load motor revolutions / Mot/load motor rev
SERVO_S110-CAN
(Pos ctrl),
SERVO_S110-DP
(Pos ctrl),
SERVO_S110-PN
(Pos ctrl)
Can be changed: C2(25) Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: DDS, p0180 Func. diagram: 4010, 4704,
4711
P-Group: Closed loop position control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 1048576 1