Internal control/status words
Function diagrams
2-821
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Fig. 2-63 2534 – Status word, monitoring functions 1
- 2534 -
Function diagram
87654321
fp_2534_98_eng.vsd
DO: SERVO
SINAMICS S110
10.07.09 V04.04.00
Internal control/status words - Status word, monitoring functions 1
Reserved
Status word, monitoring functions 1
|n_act| <= speed threshold value 2 (p2155)
|n_act| > speed threshold value 2 (p2155)
1 = n_act >= 0
Reserved
Reserved
n_act > n_max
1 = Speed setpoint - actual value deviation within tolerance t_off
Reserved
Reserved
Reserved
9
10
8
7
6
5
4
3
2
1
0
Bit No. r2197
ZSW monitoring functions 1
r2197.7
r2197.6
r2197.2
r2197.1
r2197.3
<1> n
act
= smoothed speed actual value r2169 [8010.2].
<1>
<1>
From speed signals 2 [8011.8]
From speed signals 1 [8010.4]
1
4000.00 μs
From speed signals 2 [8011.8]
From speed signals 1 [8010.6]