Fault value (r0949, decimal interpretation):
Drive object with enabled closed-loop control.
Remedy: Withdraw the pulse enable on all drives and re-activate the motor data identification.
F08510 (A) COMM BOARD: Send configuration data invalid
Message value: %1
Drive object: CU_S110-CAN, CU_S110-DP, CU_S110-PN
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: COMM BOARD did not accept the send-configuration data.
Fault value (r0949, decimal interpretation):
Return value of the send-configuration data check.
Remedy: Check the send configuration data.
Reaction upon A: NONE
Acknowl. upon A: NONE
A08526 (F) PROFINET: No cyclic connection
Message value: -
Drive object: CU_S110-CAN, CU_S110-DP, CU_S110-PN
Reaction: NONE
Acknowledge: NONE
Cause: There is no connection to a PROFINET controller.
Remedy: Establish the cyclic connection and activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000, r61001).
Reaction upon F: NONE
Acknowl. upon F: IMMEDIATELY
A08565 CBE20: Consistency error affecting adjustable parameters
Message value: -
Drive object: CU_S110-CAN, CU_S110-DP, CU_S110-PN
Reaction: NONE
Acknowledge: NONE
Cause: A consistency error was detected when activating the configuration (p8925 = 1) for the PROFINET interface.
The currently set configuration has not been activated.
Possible causes:
- IP address, subnet mask or default gateway is not correct
- IP address or station name used twice in the network
- station name contains invalid characters, etc.
See also: p8920 (PN Name of Station), p8921 (PN IP address of station), p8922 (PN Default Gateway of Station),
p8923 (PN Subnet Mask of Station)
Remedy: Check the required interface configuration (p8920 and following), correct if necessary, and activate (p8925 = 1).
See also: p8925 (PN interface configuration)
F08700 (A) CAN: Communications error
Message value: %1
Drive object: All objects
Reaction: OFF3 (NONE, OFF1, OFF2)
Acknowledge: IMMEDIATELY
Cause: A CAN communications error has occurred.
Fault value (r0949, decimal interpretation):
1: The error counter for the send telegrams has exceeded the BUS OFF value 255. The bus disables the CAN con-
troller.
- bus cable short circuit.
- incorrect baud rate.
- incorrect bit timing.