Parameter
List of parameters
1-70
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Enter the inductance of a filter connected at the power unit output.
Dependency: This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the
power unit.
Note: The parameter cannot be changed if the power unit has an internal sine-wave filter.
Description: Enters the capacitance of a sine-wave filter connected at the power unit output.
Dependency: This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the
power unit.
Note: The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
The parameter cannot be changed if the power unit has an internal sine-wave filter.
Description: Displays the internal resistance of the power unit (IGBT and line resistance).
Note: For a parallel circuit, the value corresponds to the resistance of a power unit.
Description: Sets the cooling type for booksize compact power units.
This therefore defines whether for these power units, the internal air cooling is shut down and instead, the "Cold-
Plate" cooling type is used.
Value: 0: Air cooling int
1: Cold-Plate
Note: For booksize compact power units, there is a 4 at the 5th position in the Order No.
The parameter is irrelevant for all other power unit types.
p0233 Power unit motor reactor / PU mot reactor
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(2), U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dynamic index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [mH] 1000.000 [mH] 0.000 [mH]
p0234 Power unit sine-wave filter capacitance / PU sine filter C
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(2), U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dynamic index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [µF] 1000.000 [µF] 0.000 [µF]
r0238 Internal power unit resistance / PU R internal
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
p0249 Power unit cooling type / PU cool type
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(1, 2) Calculated: - Access level: 4
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0