List of parameters
Parameter
1-289
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
4: CAN
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Sets the communication protocol for the field bus interface.
Value: 0: No protocol
1: USS
3: PROFIBUS
Note: Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
Description: Displays the effective control word 1 (STW1) of the drive for the master control.
Notice: The master control only influences control word 1 and speed setpoint 1. Other control words/setpoints can be trans-
ferred from another automation device.
Note: OC: Operating condition
p2030 Field bus int protocol selection / Field bus protocol
CU_S110-CAN Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 4 4
p2030 Field bus int protocol selection / Field bus protocol
CU_S110-DP Can be changed: T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 3
r2032 Master control, control word effective / PcCtrl STW eff
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Operation enable Yes No -
04 Ramp-function generator enable Yes No -
05 Start ramp-function generator Yes No -
06 Speed setpoint enable Yes No -
07 Acknowledge fault Yes No -
08 Jog bit 0 Yes No 3030
09 Jog bit 1 Yes No 3030
10 Master ctrl by PLC Yes No -