Siemens SINAMICS S110 - p0627[0...n] Motor overtemperature, stator winding; Mot T_over stator; p0628[0...n] Motor overtemperature rotor winding; Mot T_over rotor; r0630[0...n] Motor temperature model ambient temperature; MotTMod T_amb.; r0631[0...n] Motor temperature model, stator core temperature; MotTMod T_core

Siemens SINAMICS S110
1288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter
List of parameters
1-138
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Defines the rated overtemperature of the stator winding referred to the ambient temperature.
Dependency: For 1LA5 and 1LA7 motors (refer to p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
Description: Defines the rated overtemperature of the squirrel cage rotor referred to ambient temperature.
Dependency: For 1LA5 and 1LA7 motors (refer to p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
Description: Displays the ambient temperature of the motor temperature model.
Description: Displays the stator core temperature of the motor temperature model.
Description: Displays the stator winding temperature of the motor temperature model.
p0627[0...n] Motor overtemperature, stator winding / Mot T_over stator
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: 21_2 Unit selection: p0505
Not for motor type: PEM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
20 [K] 200 [K] 80 [K]
p0628[0...n] Motor overtemperature rotor winding / Mot T_over rotor
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(3), U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: 21_2 Unit selection: p0505
Not for motor type: PEM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
20 [K] 200 [K] 100 [K]
r0630[0...n] Motor temperature model ambient temperature / MotTMod T_amb.
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: 21_1 Unit selection: p0505
Not for motor type: PEM, REL, FEM Scaling: p2006 Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]
r0631[0...n] Motor temperature model, stator core temperature / MotTMod T_core
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: 21_1 Unit selection: p0505
Not for motor type: PEM, REL, FEM Scaling: p2006 Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]
r0632[0...n] Motor temperature model, stator winding temperature / MotTMod T_copper
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: 21_1 Unit selection: p0505
Not for motor type: PEM, REL, FEM Scaling: p2006 Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]