List of faults and alarms
Faults and alarms
3-1235
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
F50511 FBLOCKS: Memory no longer available for free function blocks
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: When the free function blocks were activated, more memory was requested than was available on the Control Unit.
Remedy: Deactivate again the drive object on which the function module "free function blocks" was last activated
(p0108[0...15].18 = 0). Then carry out a POWER ON.
Note:
The assignment of drive object numbers to the index numbers of p0108[0...15] can be read out in p0101[0...15]; the
assignment to the drive object types can be read out in p0107[0...15] on the drive object of the CU or CX (only with
SM150).
A50513 (F) FBLOCKS: Run sequence value already assigned
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: An attempt was made to assign a run sequence value already assigned to a function block on this drive object to
another additional function block on the same drive object. A run sequence value can only be precisely assigned to
one function block on one drive object.
Remedy: Set another value that is still available on this drive object for the run sequence.
Reaction upon F: NONE
Acknowl. upon F: IMMEDIATELY
A50514 FBLOCKS: Sampling time of fixed run-time group differs
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The sampling time of a system function was set to a value (p0112, p0115) lower than the smallest permissible sam-
pling time that is allowed for the fixed run-time group belonging to this system block (1 ms). The fixed run-time group
involved is assigned as a minimum to one block.
Remedy: Using p0112 or p0115, increase the sampling time of the system function to the minimum permissible sampling time
for the run-time groups of 1 ms or change the sampling time assignment of this run-time group in p20000[0...9].
A50517 FBLOCKS: Int. meas. active
Message value: -
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: A Siemens internal measurement has been activated.
Remedy: Carry out a POWER ON (power off/on) for the Control Unit involved.
F50518 FBLOCKS: Sampling time of free run-time group differs at download
Message value: %1
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: In the STARTER/SCOUT project that was downloaded, the hardware sampling time of a free run-time group (1 <=
p20000[i] <= 256) was set to a value that was either too low or too high.
The sampling time must be between 1 ms and the value r20003 - r20002.
If the sampling time of the selected free run-time group is < 1 ms, the equivalent value of 1 ms is used.
If the value >= r20003, then the sampling time is set to the next higher or the same software sampling time >= r21003.