List of parameters
Parameter
1-77
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the rated motor current (rating plate).
Dependency: Refer to: p0349
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Notice: If p0305 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is pre-assigned
accordingly. This is not the case when commissioning the motor (p0010 = 3).
Note: When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
Description: Sets the rated motor power (rating plate).
Dependency: IECdrives (p0100 = 0): Units kW
NEMA drives (p0100 = 1): Units hp
Refer to: p0100
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Description: Sets the rated motor power factor (cos phi, rating plate).
For a parameter value of 0.000, the power factor is internally calculated and displayed in r0332.
Dependency: This parameter is only available for IEC motors (p0100 = 0).
Refer to: p0100, r0332
Caution: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
Description: Sets the rated motor frequency (rating plate).
p0305[0...n] Rated motor current / Mot I_rated
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: 6300
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]
p0307[0...n] Rated motor power / Mot P_rated
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 14_6 Unit selection: p0100
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [kW] 100000.00 [kW] 0.00 [kW]
p0308[0...n] Rated motor power factor / Mot cos_phi_rated
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.000 1.000 0.000
p0310[0...n] Rated motor frequency / Mot f_rated
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: FloatingPoint32 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Hz] 3000.00 [Hz] 0.00 [Hz]