Parameter
List of parameters
1-164
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Dependency: Refer to: p0831
Description: Sets the configuration for the motor and encoder changeover.
Note: Re bit 00:
When the bit is set and the motor has to be changed over, then p0827 must be set differently in the appropriate
motor data sets.
Re bit 02:
The bit defines whether, for an EDS changeover, the status signal Gn_ZSW.14 is suppressed (parking encoder
active).
Description: Displays the status word for the drive data set changeover.
Note: This parameter is only supplied with up-to-date values if data set changeover has been selected or is running.
Re bit 00:
The signal is only influenced when a motor changeover is set via p0827 (unequal bit numbers).
05 Feedback signal contactor 5 Closed Opened -
06 Feedback signal contactor 6 Closed Opened -
07 Feedback signal contactor 7 Closed Opened -
08 Feedback signal contactor 8 Closed Opened -
09 Feedback signal contactor 9 Closed Opened -
10 Feedback signal contactor 10 Closed Opened -
11 Feedback signal contactor 11 Closed Opened -
12 Feedback signal contactor 12 Closed Opened -
13 Feedback signal contactor 13 Closed Opened -
14 Feedback signal contactor 14 Closed Opened -
15 Feedback signal contactor 15 Closed Opened -
p0833 Data set changeover configuration / DS_chng config
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: C2(15) Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 8575
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Contactor changeover from the applica-
tion/drive
application Drive -
01 Pulse suppression by application/drive application Drive -
02 Suppress drive parking for EDS changeover Yes No -
r0835.0...11 CO/BO: Data set changeover status word / DDS_ZSW
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 8575
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor changeover active Yes No 8575
01 Encoder changeover active Yes No -
02 Internal parameter calculation active Yes No -
04 Armature short circuit active Yes No -
05 Identification running Yes No -
06 Friction characteristic record running Yes No -
07 Rotating measurement running Yes No -
08 Motor data identification running Yes No -
10 Wait for pulse suppression Yes No -
11 Wait for motor changeover feedback signal Yes No -