List of parameters
Parameter
1-149
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Displays the currently referred input value of the analog input.
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Note: AI: Analog Input
Description: Sets the type of the analog input.
Value: 0: Unipolar voltage input (0 V ... +10 V)
4: Bipolar voltage input (-10 V ... +10 V)
Description: Sets the scaling characteristic for the analog input.
The scaling characteristic for the analog input is defined using 2 points.
This parameter specifies the x coordinate (input voltage in V) of the 1st value pair of the characteristic.
Note: The parameters for the characteristic do not have a limiting effect.
Description: Sets the scaling characteristic for the analog input.
The scaling characteristic for the analog input is defined using 2 points.
This parameter specifies the y coordinate (percentage) of the 1st value pair of the characteristic.
Note: The parameters for the characteristic do not have a limiting effect.
r0755 CO: CU analog input actual value in percent / CU AI value in %
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 2040
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p0756 CU analog input type / CU AI type
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: 2040
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 4 4
p0757 CU analog input characteristic value x1 / CU AI char x1
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 2040
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-11.000 [V] 11.000 [V] 0.000 [V]
p0758 CU analog input characteristic value y1 / CU AI char y1
CU_S110-CAN,
CU_S110-DP,
CU_S110-PN
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dynamic index: - Func. diagram: 2040
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 0.00 [%]