SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Dependency: Refer to: p2292
Description: Sets the signal source for the offset of the output limiting of the technology controller.
Description: Setting to invert the fault signal of the technology controller.
The setting depends on the type of control loop.
Value: 0: No inversion
1: Inversion
Caution: If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note: The correct setting can be determined as follows:
- inhibit the technology controller (p2200 = 0).
- increase the motor speed and in so doing, measure the actual value signal (of the technology controller).
- if the actual value increases with increasing motor speed, then the inversion should be switched out.
- if the actual value decreases with increasing motor speed, then the inversion should be set.
If value = 0:
The drive reduces the output speed when the actual value rises (e.g. for heating fans, intake pump, compressor).
If value = 1:
The drive increases the output speed when the actual value increases (e.g. for cooling fans, discharge pumps).
Description: Displays the status word of the technology controller.
p2299[0...n] CI: Technology controller limit offset / Tech_ctrl lim offs
SERVO_S110-CAN
(Tech_ctrl),
SERVO_S110-DP
(Tech_ctrl),
SERVO_S110-PN
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0
p2306 Technology controller fault signal inversion / Tec_ctrl fault inv
SERVO_S110-CAN
(Tech_ctrl),
SERVO_S110-DP
(Tech_ctrl),
SERVO_S110-PN
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
r2349.0...11 CO/BO: Technology controller status word / Tec_ctrl status
SERVO_S110-CAN
(Tech_ctrl),
SERVO_S110-DP
(Tech_ctrl),
SERVO_S110-PN
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Technology controller de-activated Yes No -
01 Technology controller limited Yes No -
02 Technology controller, motorized potentiom-
eter limited max.
Yes No -
03 Technology controller, motorized potentiom-
eter limited min.
Yes No -