List of parameters
Parameter
1-211
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the configuration for the extended ramp-function generator.
Caution: Re bit 00 = 1:
If the ramp-up time is longer than the ramp-down time (p1120 > p1121), then there is an acceleration step at the
zero crossover. This can have a negative impact on the mechanical system.
Note: Re bit 00 = 1:
When the direction change is changed there is no rounding-off before and after the zero crossover.
Description: Sets the signal source for "setpoint 2 enable".
Description: Sets the signal source for speed setpoint 1 of the speed controller.
Dependency: The effectiveness of this setpoint depends on, e.g. STW1.4 and STW1.6.
Refer to: r0002, p0840, p0844, p0848, p0852, p0854, r0898, p1140, p1142, p1160, r1170, p1189, p1414, p1417,
p1418
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for speed setpoint 2 of the speed controller.
Dependency: Refer to: p1155, r1170
p1151[0...n] Ramp-function generator configuration / RFG config
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: DDS, p0180 Func. diagram: 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Disable rounding-off at the zero cross-over Yes No 3070
p1152 BI: Setpoint 2 enable / Setp 2 enab
SERVO_S110-CAN
(Extended brk),
SERVO_S110-DP
(Extended brk),
SERVO_S110-PN
(Extended brk)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 2711, 4015
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 899.15
p1155[0...n] CI: Speed controller speed setpoint 1 / n_ctrl n_set 1
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 1550, 3080,
5030, 6031
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 0
p1160[0...n] CI: Speed controller speed setpoint 2 / n_ctrl n_set 2
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 1550, 3080
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 0