Signals and monitoring functions
Function diagrams
2-943
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Fig. 2-172 8016 – Thermal monitoring, motor
- 8016 -
Function diagram
87654321
fp_8016_98_eng.vsd
DO: SERVO
SINAMICS S110
16.11.10 V04.04.00
Signals and monitoring functions - Thermal monitoring, motor
Mot T_environment
p0625[M]
Thermal
3-mass-model
(for induction motors
only)
Rated motor temperature rise
MotTMod T_environ
r0630[M]
Calculated motor temperatures
Mot temp_sensortyp
p0601[M]
Model tracking
Nur
bei
KTY
Temperature sensor
via BICO connection
from encoder 1
[4704.8]
Mot T_on iron
p0626[M]
Mot T_on stator
p0627[M]
Mot T_on rotor
p0628[M]
MotTMod T_iron
r0631[M]
MotTMod T_copper
r0632[M]
MotTMod T_rotor
r0633[M]
1 = PTC alarm and time
3 = KTY84 & PTC, for
encoder only
2 = KTY84
0 = No sensor
Mot temp_sensor
p0600[M]
0
1
10
1.00 s
r0035
T_mot gemessen
T0
p0606[M]
A07910
"Motor overtemperature"
F07011
"Motor overtemperature"
<1>
[2548.2]r2135.14
A07820 "Temperature sensor not connected"
A07015
"Motor temperature
sensor fault alarm"
A07016
"Motor temperature
sensor fault, fault"
-140 °C 250 °C
Mot temp_sens time
p0607[M]
<2>
0
1
Mot_temp fault thresh
p0605[M]
&
KTY sensor type
(threshold not applicable for PTC)
1
1
[2548.2]r2135.12
T0
<4>
KTY PTC
Sensor type
Mot_temp AlrmThresh
p0604[M]
0
1
<3>
M I N
Mot temp alarm 1
p0616[M]
<5>
1650
<1> For KTY and PTC, the value p0606 = 0 has a different meaning:
KTY: 0 The output of the timer is always switched out (logical 0)
PTC: 0 Delay time = 0 s
<2> As for the switch-in delay, refer to [1024]. p0607 = 0 suppresses fault F07016.
<3> For KTY and "No sensor", temperature as defined in the model.
<4> P0606 does not work for alarms via p0616.
<5> The relevant rated response temperature in °C depends on the temperature sensor chosen by the motor manufacturer.
1
from Motor Modules
or CUA31
11
192 ms