List of parameters
Parameter
1-325
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description: Sets the hysteresis speed (bandwidth) for the signal "f or n / v comparison value reached or exceeded" (BO:
r2199.1).
Dependency: Refer to: p2141, r2199
Description: Sets the signal source for the negated enable (0 = enable) of the motor stall monitoring.
Dependency: Refer to: p2163, p2164, p2166, r2197, r2198
Refer to: F07900
Note: If the enable signal is connected to r2197.7 then the stall signal is suppressed if there is no speed setpoint - actual
value deviation.
Description: Displays the system runtime in days when the alarm occurred.
Dependency: Refer to: r2110, r2114, r2122, r2123, r2124, r2125, r2134, r2146, r3121, r3123
Notice: The time comprises r2145 (days) and r2123 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Description: Displays the system runtime in days when the alarm was cleared.
Dependency: Refer to: r2110, r2114, r2122, r2123, r2124, r2125, r2134, r2145, r3121, r3123
Notice: The time comprises r2146 (days) and r2125 (milliseconds).
Note: The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
p2142[0...n] Hysteresis speed 1 / n_hysteresis 1
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: FloatingPoint32 Dynamic index: DDS, p0180 Func. diagram: 8010
P-Group: Messages Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 300.00 [rpm] 2.00 [rpm]
p2144[0...n] BI: Motor stall monitoring enable (negated) / Mot stall enab neg
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 8012
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
r2145[0...63] Alarm time received in days / t_alarm recv days
All objects Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 8065
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r2146[0...63] Alarm time removed in days / t_alarm res days
All objects Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: 8065
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -